BC 160 |
|
Rated
current |
16
A - 160 A |
|
Rated
operating voltage |
max. 690 V a.c. |
|
Rated
frequency |
50
- 60 Hz |
|
Utilization category (switching mode) / 690 V a.c. |
AC-3 |
|
Rated
short-circuit ultimate breaking capacity / 230 V |
40
kA |
| |
25
kA |
|
Rated
short-circuit ultimate breaking capacity / 500 V |
12
kA |
|
Rated
short-circuit ultimate breaking capacity / 690 V |
6
kA |
|
Rated
short-circuit making capacity / 230/400 V |
52
kA |
|
Width |
75
|
|
Depth |
70
mm + 23 mm |
|
Height |
130 |
|
|

|
|
|
BD 250 |
|
Rated operating current |
100 A,
160 A, 200A, 250A |
|
Rated operating voltage |
690 V
a.c. |
|
Rated frequency |
50 - 60
Hz |
|
Utilization category (switching mode) / 690 V a.c. |
AC-23B
|
|
Rated short-circuit ultimate breaking capacity / 230
V |
60 kA /
100 kA |
| |
36 kA /
65 kA |
|
Rated short-circuit ultimate breaking capacity / 500
V |
16 kA /
25 kA |
|
Rated short-circuit ultimate breaking capacity / 690
V |
10 kA /
13 kA |
|
Rated short-circuit making capacity / 230/400 V |
75 kA /
140 kA |
|
|

|
|
|
BH 630 |
|
Rated
operating current |
250A, 400A, 630A |
|
Rated
operating voltage |
max. 690 V a.c. |
|
Rated
frequency |
50
- 60 Hz |
|
Utilization category (switching mode) / 690 V a.c. |
AC-23B |
|
Rated
short-circuit ultimate breaking capacity / 230 V |
60
kA / 100 kA |
| |
36
kA / 65 kA |
|
Rated
short-circuit ultimate breaking capacity / 500 V |
20
kA / 35 kA |
|
Rated
short-circuit ultimate breaking capacity / 690 V |
15
kA / 20 kA |
|
Rated
short-circuit making capacity / 230/400 V |
75
kA / 140 kA |
|
Width |
140
mm |
|
Height |
275
mm |
|
Depth |
105
mm |
|
|

|
|
|
BL 1000 |
|
Rated operating current |
315,
630, 800, 1000 A |
|
Rated operating voltage |
max.
690 V |
|
Rated frequency |
50 - 60
Hz |
|
Utilization category (switching mode) / 690 V a.c. |
AC-23B
|
|
Rated short-circuit ultimate breaking capacity / 230
V |
85 kA
|
| |
65 kA
|
|
Rated short-circuit ultimate breaking capacity / 500
V |
45 kA
|
|
Rated short-circuit ultimate breaking capacity / 690
V |
20 kA
|
|
Rated short-circuit making capacity / 230/400 V |
140 kA
|
|
Width |
210
|
|
Height |
350
|
|
Depth |
135 +
63 mm |
|
|

|
|
|
BL 1600 |
|
Rated current |
630,
1000, 1250, 1600 A |
|
Rated operating voltage |
max.
690 V a.c. |
|
Rated frequency |
50 - 60
Hz |
|
Utilization category (switching mode) / 690 V a.c. |
AC-23B
|
|
Rated short-circuit ultimate breaking capacity / 230
V |
85 kA
|
| |
65 kA
|
|
Rated short-circuit ultimate breaking capacity / 500
V |
45 kA
|
|
Rated short-circuit ultimate breaking capacity / 690
V |
20 kA
|
|
Rated short-circuit making capacity / 230/400 V |
140 kA
|
|
Width |
210 mm
|
|
Height |
350 mm
|
|
Depth |
135 mm
+ 63 mm |
|
|

|
|
 |